Applying and exam day
G-60 Practice Questions With Answers Explained
Ten original G-60 practice questions on permits, torches, LPG and acetylene cylinders, leak checks and fire watch, each tied to the FDNY booklet.
Published · 5 min read · Facts last verified October 12, 2026
Studying for the exam? Try our G-60 practice test, with free sample questions written from the FDNY's study material.
Below are ten original practice questions for the G-60 Certificate of Fitness exam (Torch Use of Flammable Gases), each with the answer and the section of the FDNY study booklet it comes from. They are not real exam questions, and nobody outside the FDNY has those. They are written to the same format as the real exam: four choices, one best answer. They cover the parts of the booklet that cause the most trouble: permit thresholds, torch procedures, cylinder rules and the numbers you have to learn by heart.
The real G-60 exam, according to the FDNY's Notice of Exam, is 35 multiple-choice questions in 53 minutes on a touch-screen computer, and you need at least 70% to pass. That's about a minute and a half per question. Try each question below before reading the answer.
Permits and certificates
1. A contractor stores 30 cylinders of oxygen totalling about 600 SCF at a work site. What does the G-60 booklet say?
- No permit is needed for oxygen in any amount
- A permit is needed because oxygen storage over 504 SCF requires one
- A permit is needed only above 1,000 SCF
- A permit is needed only if acetylene is stored with it
Answer: B. The booklet requires an FDNY permit for oxidizing gases such as oxygen over 504 SCF, and for flammable gases over 400 SCF. (Introduction: FDNY Permits; Part 3, 3.1.6.)
2. According to the booklet's permit table, how many 16.4 oz LPG containers on a construction site require a permit?
- 46
- 54
- 20
- 23
Answer: C. The general figure is 46, but the table gives a lower number for construction sites: 20. The 14.1 oz size is 54 in general and 23 on construction sites. Expect the exam to test whether you notice the setting. (Introduction: FDNY Permits.)
Torch equipment and procedures
3. A crew stops oxygen-acetylene cutting at a construction site for a 45-minute lunch. What must happen to the cylinders?
- They must be moved to approved storage for any stop
- Only the acetylene cylinder must be moved
- They must be taken off the premises
- Nothing: breaks of up to 2 hours are an exception
Answer: D. When oxygen and acetylene torch work is not in use, including at the end of the day, the cylinders go to approved storage or off the premises. Brief interruptions of not more than 2 hours, such as lunch, are excepted. Separately, if the torch will be idle for an hour or more, its valve is closed and the gas supply shut off. (Part 2, 2.3.3 and 2.3.4.)
4. A torch starts hissing and the flame appears to be burning back inside it. What should the operator do first?
- Close the torch control valves, then the fuel gas container valve
- Open the oxygen valve fully to blow the flame out
- Pull the hose off the torch
- Spray water on the hose
Answer: A. That is a flashback. The booklet says to close the torch control valves as soon as the hissing or whistling is noticed, then close the fuel gas container valve, and let the flame burn itself out. If it happens again after cleaning and repair, a qualified technician should fix the equipment. (Part 2, 2.5.2.)
5. Unless the manufacturer says otherwise, how far should an acetylene cylinder valve be opened?
- All the way, so the torch is never starved of gas
- No more than about 1½ turns, preferably ¾ turn or less
- At least 3 full turns
- A quarter turn and then closed again
Answer: B. The booklet cites ANSI Z49.1 for this and adds that acetylene pressure must never go above 15 psi. If more acetylene is needed, use a larger hose. (Part 2, 2.3.2; Part 3, 3.1.2.)
Cylinders, gases and leaks
6. Oxygen and acetylene are stored on the floor where torch work is happening. How far must that storage be from an air compressor?
- 10 feet
- 20 feet
- 25 feet
- 50 feet
Answer: D. The booklet's distances for this storage are 20 feet from flammable and combustible liquids, oxidizing gases and readily combustible materials; 25 feet from open flames and other ignition sources; and 50 feet from air-conditioning equipment, air compressors, ventilation intakes and other flammable gas storage. (Part 3, 3.1.5.)
7. Why is an LPG leak more dangerous than a CNG leak, according to the booklet?
- LPG is heavier than air and collects low; natural gas is lighter and disperses
- LPG is toxic and natural gas is not
- LPG has no odor added and CNG does
- CNG cannot burn
Answer: A. LPG sinks and spreads along the ground, while natural gas tends to rise and escape. Both are odorized, and LPG is described as non-toxic but able to cause suffocation. (Part 3, 3.3.1 and 3.4.)
8. After connecting a new cylinder, you see ice forming on the cylinder's own control valve. What should you do?
- Chip the ice off and keep working
- Return the cylinder to the supplier next week
- Call 911 immediately
- Warm the valve with the torch
Answer: C. Ice means gas is leaving the cylinder as a liquid, which points to a dangerous defect. If the ice is on the appliance or connectors, shut the main valve, take the cylinder out of service and return it to the supplier. If it is on the cylinder or its valve, call 911 right away. (Part 3, 3.5.)
Hot work rules and fire watch
9. Torch cutting is done in a building's mechanical room. It is not a construction site or a roof, and the contractor holds a site-specific permit. Which statement matches the booklet?
- No fire watch is needed indoors
- A fire watch is needed, but it doesn't have to be an F-60 holder
- The torch operator can watch his own work
- Two F-60 fire guards are required
Answer: B. Every hot work operation needs a fire watch with no other duties. The booklet requires an F-60 fire guard only at construction sites, on rooftops and torch-applied roofing jobs, and in buildings where a citywide permit holder is doing the torch work, and it stresses that not every fire watch must hold an F-60. (Part 1, 1.4.1 and 1.4.2.)
10. Arc welding finishes at 2:00 p.m. When does the booklet require the follow-up inspections?
- Only one, at 2:15 p.m.
- At 2:30 p.m. and 3:00 p.m.
- At 3:00 p.m. and 5:00 p.m.
- The next morning before work starts
Answer: B. For CNG, LPG or arc welding hot work, the first inspection is 30 minutes after the work is completed and the second is 1 hour after, to catch smoldering fires. The fire watch itself lasts at least 30 minutes after the work stops. (Part 1, 1.4.4.)
How did you do?
If you got 7 or more right, you are on the right track. The real exam's 70% bar works out to 25 of 35. If the numbers tripped you up, you're not alone: the G-60 booklet is dense with thresholds (16.4 oz, 8.7 SCF, 400 and 504 SCF, 15 psi, 30-foot hoses, 20/25/50-foot separations). Go back to the booklet itself, then see our G-60 exam guide for a part-by-part summary.
For more questions like these, the G-60 practice page has a free sample, and the full G-60 bank with explanations, practice by topic and timed 35-question mocks is on the pricing page. Some of the bank's fire watch, permit and extinguisher questions also appear in our F-60 bank, because the two FDNY booklets set out the same rules.
Practice for the exam
Original questions written from the FDNY's free study material, with an explanation for every answer. Not real exam questions, and no promise about any result.
Sources
- Study Material for the Certificate of Fitness Examination for Use of Flammable Gases with Oxygen or Use of LPG/CNG for Hot Work Operations (Citywide) G-60 — New York City Fire Department (FDNY). Accessed October 12, 2026. Revised January 2026 (Contact/Payment info)
Fire Guard Test is an independent practice resource. We are not affiliated with, endorsed by, sponsored by, or connected to the New York City Fire Department (FDNY), the City of New York, or any accredited school or training provider. "FDNY" is a trademark of the City of New York and is used here only to describe the exams our practice material helps you prepare for. Every question here is original, written from the study material the FDNY publishes free of charge; none is a real exam question, and our mock exams are not identical to the real exam. Exam rules, fees and study material can change without notice, so always check the current official study material and Notice of Exam on nyc.gov before your test. Practicing here does not guarantee that you will pass or be issued a Certificate of Fitness, and nothing on this site is legal or fire-safety compliance advice.
Exam rules, fees and study booklets change. Check the current FDNY study material and Notice of Exam for your certificate before you rely on anything here.